Date of Award
2016
Document Type
Thesis
Publication Status
Version of Record
Submission Date
October 2026
Thesis/Dissertation Advisor [Chair]
Meeroff, Daniel E.
Abstract
Calcium carbonate precipitation and formation of clog particles inside the leachate collection pipe can cause catastrophic failures in landfill operation. This study focuses on quantifying the effectiveness of electronic scale control to reduce the clog formation within the pipe network. A field scale model (40ft × 20ft) was constructed, featuring side-by-side flow of electronically treated and untreated composite leachate. Data obtained in the first phase of this study indicate that electronic scale control system does not have any statistically significant effect on water quality parameters. The second phase of this study identified calcite (CaCO3) to be the predominant phase present in the precipitates using XRD/XRF diffraction pattern analyzed through a search match calculation program (MATCH! Version 3.2.0) which concur with the previous studies. Furthermore, Rietveld refinement using FullProf Suite confirms that there were no differences between the treated and untreated precipitate based on the phases identified in the respective samples.
Extent
135 p.
Recommended Citation
Shaha, Bishow Nath, "Effect of Electronic Water Treatment System on Calcium Carbonate Scaling" (2016). Electronic Theses and Dissertations 2010 - 2019. 1445.
https://digitalcommons.fau.edu/etd_general_6/1445
Identifier
FA00004706
Comments
Includes bibliography.|Thesis (M.S.)--Florida Atlantic University, 2016.|FAU Electronic Theses and Dissertations Collection|Includes bibliography.